Guide to selection and use of anti-condensation heaters
The power rating required to prevent condensation in a given cubicle depends upon a number of factors, including  ambient temperature and relative humidity. However, as a general guide, 10 watts per square metre of cubicle surface area may be used.

Thermostats
We recommend the use of a separate thermostat fitted within the cubicle but away from direct radiation from the heater (see thermostats page).

Mounting
To ensure best results, the heaters should be mounted on the back plate of the enclosure with the resistor horizontal, and the terminals at the bottom. This will ensure a free flow of air over the heater.If it is not possible to mount the heater in this way, or if the air flow is severely restricted, it may be necessary to use heat resisting cable to connect the heaters.


 Ref.    A    B    Standard range of watts    Standard voltages

 ACH20    65    19    20, 30    110, 230 volts
 ACH60    121    70    20, 40, 60, 80    110, 230 volts
 ACH100    191    146    80, 100, 120    110, 230 volts

When ordering, please specify reference number, watts and operating voltage
e.g. ACH 60 - 40 watts - 230 volts.